3 phase cable size calculator

This tool provides an engineering estimate only. Always verify with local electrical code, derating tables, and manufacturer data.

How this 3 phase cable size calculator works

This calculator estimates the cable cross-sectional area (mm²) for a three-phase circuit using two core checks: ampacity (current-carrying capacity) and voltage drop. The larger requirement is selected, then a design margin is applied, and finally the nearest standard cable size is recommended.

You can calculate from either:

  • Load power in kW (with power factor and efficiency), or
  • Load current directly in amps.

Formulas used

1) Three-phase current from power

For power-based input, load current is estimated using:

I = P / (√3 × V × PF × η)

where P is watts, V is line-to-line voltage, PF is power factor, and η is efficiency (decimal).

2) Ampacity-based minimum area

A simplified current-density method is used:

Aampacity = I / (J × Ktemp)

J is a typical current density (A/mm²) chosen by material and installation method, and Ktemp is ambient correction.

3) Voltage-drop-based minimum area

A practical approximation for 3-phase voltage drop is applied:

Avd = (√3 × I × ρ × L) / ΔV

where ρ is conductor resistivity, L is one-way length, and ΔV is allowed voltage drop in volts.

Why both checks matter

A cable that survives current thermally may still fail voltage-drop requirements. Likewise, a cable sized for low voltage drop might be larger than thermal minimum. Good design requires both checks, then selecting the greater value.

Quick design guidance

  • Long feeders: voltage drop usually drives cable size.
  • High ambient temperature: thermal capacity drops, so cable size increases.
  • Aluminium conductors: usually require larger cross-section than copper for the same duty.
  • Motor loads: include power factor and efficiency to avoid underestimating current.
  • Safety margin: include future expansion and real-world installation effects.

Worked example

Suppose you have a 45 kW motor on 415 V three-phase supply, PF = 0.9, efficiency = 95%, 50 m run, copper cable, 3% voltage drop limit. The calculator first finds load current, then checks ampacity and voltage drop. After adding margin, it rounds up to the next standard size.

This mirrors a typical design workflow used in preliminary sizing before detailed code checks.

Important limitations

This is a preliminary estimator. Final cable sizing should include:

  • National/regional code tables (IEC, NEC, BS, AS/NZS, etc.)
  • Grouping factors and installation-specific derating
  • Harmonics, starting current, duty cycle, and fault level/short-circuit withstand
  • Insulation rating and termination temperature limits
  • Protective device coordination

FAQ

Is this calculator suitable for final sign-off drawings?

No. Use it for fast estimation only, then verify with standards and project-specific data.

Why does cable size jump quickly for long distances?

Because voltage drop scales with current and length. Longer runs often need much larger conductors.

Can I use this for aluminium armoured cable?

Yes for rough sizing. But always confirm exact cable construction and tabulated ratings from manufacturer/code tables.

🔗 Related Calculators